29
/
en
AIzaSyAYiBZKx7MnpbEhh9jyipgxe19OcubqV5w
April 1, 2024
2163396
181050
2

23h 44min, aug 24, 2016 y - 1A Stator Cooling Pump Seal Failure

Description:

1A Stator Cooling Pump seal failure. Personnel was dispatched to Stator Cooling due to Control Room receiving Stator Cooling Water Tank High/Low alarm. Personnel reported tank level low, seal failure on 1A Stator Cooling Pump, and smoke in the area of stator cooling. Pumps were swapped, 1B placed in service, 1A pump removed from service, and the 1A suction valve closed to stop leak. Level raised in stator cooling tank and alarm cleared. Personnel reported that the 1A pump temperature was excessive and the smoke in the area was coming from 1A stator cooling pump seal failure and the high temperature of pump. Repair seal failure as well as evaluate effects of high temperature. CR10265050

Added to timeline:

16 Nov 2018
0
0
231
Stator Water Filter
KT Analysis

Date:

23h 44min, aug 24, 2016 y
Now
~ 7 years and 8 months ago
PremiumAbout & FeedbackTermsPrivacy