5 St 22 Nov 2010 Jahr - 1N43D003-Created in Error
Beschreibung:
CR105721
2010114843, Stator Cooling Water Generator inlet filter, 1N43-D003, appears to be stopping up. The DP on this filter has has gone up by approx. 1 psid per day over the last 3 days. The DP on D003 at this time is 6 psid. If the DP continues to rise, it could cause a low flow condition to the generator. Please investigate and repair.
**note - this CR was submitted in error. The permanently installed guage does not read accurately and is to be repaired under WO 1100592001. Temporary guages are installed and show a d/p of ~3psid, which is unchanged over a period of many days. No further action required. cew 11/22/10**
WHAT IS AFFECTED: Possibility of causing low flow to the generator.
HOW DISCOVERED: Inside rounds SO performing checks to satisfy Compensatory Action 1-10-041